This page is printable and fits in 1 A4 paper.
 Examples

Rectangular Weir
This is an example of a Rectangular weir application. The transducer is mounted 1000mm above the bottom of the rectangular weir, this is the Empty Distance. The Span is 600mm and the Blanking Distance is 400mm (min is 350mm). The transducer must be fitted 3 x head upstream. There is an external counter connected to the relay counter.

The water flow must not dam up and cause a build up behind the weir.

Please note! The Empty Distance is to the bottom of the plate and not the bottom of the weir.
 Parameter List

SECURITY CODE
SELECT
EMPTY DISTANCE
SPAN
BLANKING
RATE OF CHANGE
FAIL TIMER
FAILSAFE MODE
FLOW CURVE
FLOW UNITS
MAXIMUM FLOW
SET UP RELAYS
RELAY 1
RELAY 2
RELAY 1 COUNTER
RELAY 2 HIGH
RELAY 2 RESET
TOTALISER RESET
ZERO OFFSET
OFFSET
USE TEMP COMP
SET NEW PASSWORD
FACTORY RESET
5159
mm
1000mm
600mm
400mm
1000mm/min
300
Hold
Yes
Rectangle weir
M3/hour
145
Yes
Counter
High
10000
500
490
No
No
0
No
No
Below is what EASZ-11 will display on the above application.

FI = 750 It/sec
TI 2345665
and
Head 1000mm
TI 2345665

Now the display will toggle when the ENTER key is pressed. The relay will drive the counter for every 10000 counts.

The analogue output should be approximately 19.1 mA.

Copyright 2002 EESIFLO http://www.eesiflo.com