The relays can be used either for an external counter, high
alarm or a low alarm. The difference is that a high alarm
has its reset below the setpoint, and a low alarm has its
reset above the setpoint.
DEFAULT Off
As above.
DEFAULT Off
The external counter or sampler can be set here. Select the
amount of counts before the sampler will be activated.
DEFAULT 1000
| Relay
1 High or Low depending upon selection |
This is the setting for the High or the Low alarm depending
on which is selected.
DEFAULT 0.00mm
This is where you can enter the reset. Please note that if
it is a high alarm then the reset must be below and if it
is a low alarm then the reset must be above the setting.
DEFAULT 0.00mm
| Relay
2 High or Low depending upon selection |
As above.
DEFAULT 0.00mm
As above.
DEFAULT 0.00mm
The totaliser can be reset here.
DEFAULT No
Should there be a small offset at the Zero this prompt can
be used to offset it.
DEFAULT No
Up to a maximum of 50 mm minus and positive.
DEFAULT 0mm
| Use Temperature
Compensation |
Select Yes only if a EESIFLO10C is used or a Temperature Transducer
is connected.
DEFAULT No
This prompt will allow you to change the default factory password.
DEFAULT No
This prompt will reset all values entered back to factory
settings including the password. Please write down all settings
before using this function.
DEFAULT No
|
|