| Setting
up the Temperature Sensors (Continue) |
Press Enter to accept the No measuring
inputs for all 4 of Channel B's inputs
B: T-Inlet (Outlet,
T3 and T4)
No measuring |
 |
|
You will be returned to the Special Function Proc. Inputs,
menu. Press the BRK key once to return to the main
menu
| Defining
Watts or Joules as the units of output for Heat Flow |
The following steps define the units of output for the
Heat Flow measurements as either Watts or Joules
- On the Main Menu select SF (Special Function)
then press ENTER
- Using the 2 and 8 keys, scroll up or down
until SYSTEM setting appears then press ENTER
- Using the 2 and 8 keys, scroll up or down
until Measuring appears then press ENTER
- When Flow Velocity >NORMAL< uncorr. appears,
press ENTER
- When Cut-off Flow >ABSOLUT< sign appears,
press ENTER
- When Cut-off Flow >FACTORY< user appears,
press ENTER
- When Velocity limit 25.0 m/s appears, press ENTER
- When Heat Quantity [J] > [Wh]< appears,
use the 4 and 6 keys to switch between J
(Joules) or Wh (Watts) then press ENTER
- When heat+flow quant. Off >ON< appears,
press ENTER
- When Quant. wrapping >Off< on appears,
press ENTER
- Press the BRK key once to return to the Main
Menu
| Defining
Heat Flow as the Output for Channel A |
- From the Main Menu, using the 4 and 6
keys, scroll left or right until the OPT (Output)
menu is selected then press ENTER.
- Press ENTER to select Channel A.
- On the Physic. Quant. screen, using the 2
and 8 keys, scroll up or down until Heatflow
appears then press ENTER
- On the Heatflow in screen, using the 2
and 8 keys, scroll up or down and select either
W (Watts), KW (Kilowatts), MW (Megawatts)
then press ENTER
- When Damping 10 s appears, enter a value over
which you'd like your data averaged, then press ENTER
- When Store Meas. Data >NO< yes appears
press ENTER
- When Serial Output >NO< yes appears press
ENTER
- When Current Loop I1:>NO< yes appears press
b
- You will be returned to the Main Menu
| Installing
the Temperature Sensors onto the Pipes |
In the following steps we'll install the temperature sensors
onto the Inlet and Outlet pipes:
- Following the directions found on page 11-3 of
the EESIFLO 6000 Series Operating Instructions, locate
an appropriate mounting spot for a Single PT100 Temperature
Sensor on the OUTLET or DOWNSTREAM side
of the Heat Exchanger
- Following the directions found on page 11-3 in
the EESIFLO 6000 Series Operating Instructions, locate
an appropriate mounting spot for a Single PT 100 Temperature
Sensor on the INLET or UPSTREAM side
of the Heat Exchanger
|