| Setting
up the Temperature Sensors |
In the following steps we will "Link" the output
from the two temperature sensors to the Flow Transducer
installed on Channel A to produce Heat Flow Measurements.
- On the main menu, using the 4 and 6 keys,
scroll over to the SF (Special Functions) menu
and press ENTER
- Using the 2 and 8 keys, scroll up or down
until SYSTEM Setting is displayed, then press ENTER
- Using the 2 and 8 keys, scroll up or down
until Proc. Inputs appears then press ENTER
- Using the 2 and 8 keys, scroll up or down
until Link temperatures appears then press ENTER
- The following screen will appear
A: T-Inlet
Input T1 |
 |
|
The line A: T-Inlet is asking which Temperature
Sensor is installed as Channel A's Inlet temperature
sensor. If you've followed the above steps, this is by default
Input T1
Press ENTER to accept this default value and a similar
screen will appear to define Channel A's Outlet temperature
sensor as follows:
A: T-Outlet
Input T2 |
 |
|
The top line A: T-Outlet is asking which Temperature
Sensor is installed as Channel A's Outlet temperature
sensor. If you've followed the above steps, the default
is Input T2
Press ENTER to accept this value and another screen
will appear for Channel A's T3 sensor as follows:
A: T(3)
No measuring |
 |
|
The top line A: T(3) is asking which Temperature
Sensor is installed as Channel A's (T3) temperature
sensor. If you've followed the above steps, the default
No Measuring should be displayed
Press ENTER to accept this value and another screen
will appear for Channel A's T4 sensor as follows:
A: T(4)
No measuring |
 |
|
The top line A: T(4) is asking which Temperature
Sensor is installed as Channel A's (T4) temperature
sensor. If you've followed the above steps, the default
No Measuring should be displayed
Press ENTER to accept this value and another screen
will appear repeating the entire process for Channel
B. All the above screens should appear for Channel
B with the default Temperature Sensor of No measuring.
Press Enter to accept the No measuring
inputs for all 4 of Channel B's inputs
B: T-Inlet (Outlet,
T3 and T4)
No measuring |
 |
|
|